Overview
The Model 732A DC Power
Supply with Battery Back-Up provides a filtered and regulated source of
54 volts DC with a maximum output current of 2 amperes. The nominal
input voltage is 120 volts, 60 hertz. Rechargeable batteries contained
within the Model 732A provide output back-up capability in the event of
an AC input voltage interruption. Under battery operation, the Model
732A will continue to supply a 2 ampere DC output for up to nominally
three hours. For output loads of less than 2 amperes the battery
operating time will substantially increase. The unit is completely
self-contained in a compact wall-mounted cabinet. The Model 732A is
Underwriters Laboratories, Inc. LISTED under their CUL-1950 ITE
category.
Model 732A Specifications
Input Voltage:
95-135 volts, 47-63 hertz
Input Current: 2.0 amperes, maximum
Input Power Cord:
Type: 3-conductor with NEMA 5-15P plug
Length: 6 feet (2 meters), nominal, not detachable
Output Voltage:
54 volts DC, nominal, with AC input voltage present
48 volts DC, nominal, battery operation; no AC input voltage present
Output Current: 2.0 amperes continuous, maximum
Recommended Minimum Output Load Current: 50 milliamperes (helps
maintain correct charge voltage)
Output Ripple Voltage: less than 100 millivolts p-p;
“talk-battery” quality
Output Protection:
Type: solid-state, automatic reset
Batteries: 4
Type: 12 volts, 7.2 ampere-hour (Ah), sealed lead-acid (Panasonic
LC-R127R2P or equivalent), classed for transportation as “Non-Spillable”
Battery Operating Time (Nominal):
20 hours, 0.3 ampere output load
10 hours, 0.6 ampere output load
5 hours, 1.2 ampere output load
3 hours, 2 ampere output load
Battery Charge Time (Nominal):
3 hours, no output load
6 hours, 1 ampere output load
24 hours, 2 ampere output load
Figures reflect charging process beginning with batteries in fully
discharged state
Automatic Battery Disconnect:
Type: solid-state
Operating Threshold: 41 volts, nominal
Input to Output Efficiency: 80%, nominal, measured with 120 volt
60 hertz input, 2 ampere output load
Output Connector—3-Position:
Functions Supported: ground, DC output
Type: Phoenix Contact (or equivalent) pluggable terminal strip, 0.2-inch
(5.08 mm) contact centers
Mating Plug (included with Model 732A): Phoenix part number
IC2,5/3-ST-5,08 (Phoenix order number 1786187) or equivalent
Output Connector—6-Position:
Functions Supported: ground, DC output, status contact
Type: Molex® Mini-Fit, Jr.™ 6-position dual row header
Mating Connector: Molex Mini-Fit, Jr. 6-position dual row receptacle,
suggested part number 39-01-2060; suggested crimp-on female terminals
part number 39-00-0039
LED
Status Indicators: 2
Functions: AC input present, DC output present
Status Contact:
Action: normally open (not shorted)
Type: sealed bifurcated relay contact, isolated
Rating: 0.5 amperes maximum at 60 volts AC or 60 volts DC (resistive)
Function: closes (shorts) upon loss of AC input power, defined as
nominally less than 15 volts
Safety Compliance: Underwriters Laboratories, Inc. CUL-1950 ITE
LISTED
Radiated Noise Compliance: complies with FCC Part 15, subpart J,
class A for radiated and conducted emission
Operating Environment:
68 degrees F (20 degrees C), nominal. Intended for operation in
commercial environment where air conditioning is present. Operation at
temperatures greater than recommended will significantly reduce battery
life.
Dimensions (Overall):
6.3 inches high (24.8 cm)
12.4 inches wide (31.5 cm)
7.1 inches deep (18.0 cm)
Mounting: intended primarily for wall mounting
Weight:
30.5 pounds (13.8 kg)
32.4 pounds (14.7 kg), shipping weight
Specifications
subject to change without notice.

|